Coordination of residual current protective devices

From Electrical Installation Guide
Revision as of 17:01, 18 February 2011 by Wikiadmin (talk | contribs) (Created page with '{{Menu_Protection_against_electric_shocks}} <br> __TOC__ <br> Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then …')
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Home > Protection against electric shocks and electrical fires > Residual Current Devices (RCDs) > Coordination of residual current protective devices



Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then protected individually or by groups, or by a combination of both methods.
Such discrimination avoids the tripping of any RCD, other than that immediately upstream of a fault position:

  • With equipment currently available, discrimination is possible at three or four different levels of distribution :

  - At the main general distribution board
  - At local general distribution boards
  - At sub-distribution boards
  - At socket outlets for individual appliance protection

  • In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.
Discrimination between RCDs

The general specification for achieving total discrimination between two RCDs is as follow:

  • The ratio between the rated residual operating currents must be > 2
  • Time delaying the upstream RCD

Discrimination is achieved by exploiting the several levels of standardized sensitivity: 30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown in Figure F34.



FigF34.jpg





















Fig. F34: Total discrimination at 2 levels


Discrimination at 2 levels

(see Fig. F35)
Protection

  • Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic device) for protection against indirect contacts
  • Level B: RCD instantaneous, with high sensitivity on circuits supplying socket-outlets or appliances at high risk (washing machines, etc.)

Schneider Electric solutions

  • Level A: Compact or Multi 9 circuit-breaker with adaptable RCD module (Vigi NSX160 or Vigi NC100), setting I or S type
  • Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable RCD module (e.g. Vigi C60 or Vigi NC100) or Vigicompact

Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents.



FigF35.jpg











Fig. F35: Total discrimination at 2 levels


Discrimination at 3 or 4 levels

(see Fig. F36)
Protection

  • Level A: RCD time-delayed (setting III)
  • Level B: RCD time-delayed (setting II)
  • Level C: RCD time-delayed (setting I) or type S
  • Level D: RCD instantaneous

Schneider Electric solutions

  • Level A: Circuit-breaker associated with RCD and separate toroidal transformer (Vigirex RH328AP)
  • Level B: Vigicompact or Vigirex
  • Level C: Vigirex, Vigicompact or Vigi NC100 or Vigi C60
  • Level D:

  - Vigicompact or
  - Vigirex or
  - Multi 9 with integrated or adaptable RCD module: Vigi C60 or DPN Vigi
Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents



FigF36.jpg




















Fig. F36: Total discrimination at 3 or 4 levels


Discriminative protection at three levels (see Fig. F37)



FigF37.jpg











































Fig. F37: Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection

Share